- Frequently Asked Questions (FAQs):
Q1: What is the overload capacity of ABB LV generators?
A: • 10% overload at nominal power factor for one hour at twelve hour intervals
• 50% overload at nominal power factor for two minutes at twelve hour intervals
Q2: What is the voltage distortion of ABB LV generators?
A: Not exceeding 5%, as specified by IEC 60034-1, but a typical value for AMG series generators is less than 3.5% for line to line and phase to neutral voltages at noload and linear load operation.
Q3: What about voltage and frequency variation?
A: AMG industrial generators can deliver both 50 Hz and 60 Hz, and can operate at ±2% variation of rated frequency.Voltage variation is 95% - 105% of rated voltage.
Q4: How about the overcurrent capability of ABB LV generators?
A: ...