ANSI/IEC Recloser Protection & Control PCD

Standard features

  • Multi-function protection relay (see Protective Functions)
  • 54 Protection curves resident in device, including 38 traditional recloser curves
  • Three independent setting groups
  • Menu driven programming through the front panel or PC
  • Back-lit LCD display for easy reading
  • Digital metering: voltage, current, kWh, kVarh, power factor, demand watts, VARs and frequency
  • Min/Max current and power recording
  • Load Profile recording (up to 160 days at 60 min. intervals)
  • Extensive fault and operation recording
  • Fault location (three-phase only)
  • Power quality monitoring
  • Oscillographic data recording
  • DNP 3.0 Level 2, MODBUS ASCII and MODBUS RTU Communication
  • DNP 3.0 has unsolicited reporting
  • Two communication ports on the rear panel: one RS-232 and one RS-485, configurable to DNP 3.0 Level 2, MODBUS ASCII or MODBUS RTU
  • Independent front panel ports
  • RTS/CTS handshaking configuration for multiple types of radios
  • Built in programmable logic controller
  • Programmable I/O contacts
  • Integral temperature compensated battery charger
  • Local or remote battery test
  • Continuous self-checking with status indication
  • Windows based software for online or offline programming
  • Software provides remote data configuration via modems

Protective functions
  • Phase time over-current protection (51P)
  • Phase instantaneous over-current protection (50P-1, 50P-2, 50P-3)
  • Ground over-current protection (51N)
  • Ground instantaneous over-current protection (50N-1, 50N-2, 50N-3)
  • Negative sequence over-current protection (46)
  • Phase and ground directional over-current protection (67P, 67N)
  • Available with up to 38 recloser curves, nine ANSI curves, four IEC curves and three user programmable curves
  • Multishot reclosing: each reclose step allows independent programming of protective functions (79-1, 79-2, 79-3, 79-4, 79-5)
  • Reverse power detection and control (32P, 32N)
  • Undervoltage and overvoltage control and alarm (27/59)
  • Two independent steps for load shed, restoration and over frequency (81S, 81R, 81O)

Optional features
  • Single-phase operation
  • Loop feed application control logic
  • Fiber optic communications
  • Sensitive Earth fault protection
  • Package for locating control remote to recloser (up to 250’)

Enhancements
  • Standard RS-232 port on the front panel for local programming and record downloading
  • Enlarged LCD display (220% larger)
  • LCD now is automatically readable across complete temperature range (-40oC to +70oC)
  • Hot line tag button included on the front panel
  • Two programmable LED indicators on the front panel
  • DNP 3.0 implementation now has assignable points, assignable classes and unsolicited retry configuration