HECPS-S

For pump storage power plants

System Type

HECPS-3S
HECPS-5S
HECPS-5Sp
Rated maximum voltage [kV]
25.3
25.3
25.3
Rated frequency [Hz]
50 / 60
50 / 60
50 / 60
Rated power frequency withstand voltage [kV]
60 / (80)
60 / (80)
60 / (80)
Rated lightning impulse withstand voltage [kV]
125 / (150)
125 / (150)
125 / (150)
Rated current [A]: 50 Hz
up to 13500
up to 13500
up to 17500
Rated current [A]: 60 Hz
up to 12500
up to 12500
up to 16500
Rated short-circuit breaking current [kA]
100
130
130